AX-KWH-Ci1 meter is an accurate and cost effective solution for measurement and display of kWh and VAr. Its easy programming, mounting and user friendly navigation makes the Ci1 the ideal choice for customers who require reliable energy measurement. The unit is mounted in a DIN 96 panel mounted enclosure, has a backlit LCD display and user programmeable CT ratios . The unit has a series of plug modules to give either 1 or 2 pulse o/p, or a RS485 communication module that can be programmed internally to respond either to Modbus-RTU or Johnson Controls.
Product Features
• DIN 96 enclosure
• Backlit LCD screen
• Bezel depth 6.1mm
• Plug-in output modules
• Programmable CT ratio
• True RMS measurement
• User programmable system configuration
• Exceptionally cost effective

Nominal Input Voltage Range
100 to 289Vac L-N (175 to 500Vac L-L) 45-66Hz
Maximum Voltage Overload
120% of nominal
Maximum Short Duration Voltage
2 x range maximun
Nominal Burden
< 0.2VA per phase
Nominal Input Current
5A ac rms
Max Overload Current
6A
Maximum Short Duration Current
50A
Auxiliary Operating Range
110 to 400 Vac nominal +/- 10% or 120 to 350Vdc +/- 20%
Accuracy
Active energy kWh Class 1 (IEC 62053-21)

Reactive energy kVArh +/- 1% of range
Output Modules Optional
Pulsed output solid state relays 50mA @250Vac (2 max)

RS-485 2-wire half duplex (or Modbus RTU or Johnson Controls)

baud rate 2400, 4800, 9600, 19200, 38400
Enclosure
DIN 96 panel mount
Dimensions
96 x 96 x 64.1mm (depth behind panel with module 77.5mm depth)
Cutout
92 x 92 mm
Operating Temperature Range
-10 to + 55°C (0-90% RH non-condensing)
Front Protection Rating
IP52 (case rating IP 30)
Weight
300gms
Conformity
IEC 61326, IEC 61010-1, IEC 62053-21
Country of Origin
United Kingdom